What Title K is and how to use this guide
Title K of the NSR-10 (Reglamento Colombiano de Construcción Sismo Resistente, Colombia's seismic-resistant construction regulation) gathers complementary requirements for Colombian buildings, including the means of egress: doors, stairs, ramps, corridors and emergency lighting. This guide collects some minimum values that a designer or reviewer often consults, each with its numeral.
Only rules that the team marked as verified are published. No figure taken from trade practice or from secondary sources appears, and one figure for stairs in single-family housing that contradicts another in the same numeral was left out.
Evacuation doors
| Numeral | Rule | Value | Applies to |
|---|---|---|---|
| K.3.8.2.1 | Evacuation door: minimum clear width (700 mm in a bedroom) | 800 mm | General |
| K.3.8.2.1 | Evacuation door: minimum clear height | 2 m | General |
Stairs
| Numeral | Rule | Value | Applies to |
|---|---|---|---|
| K.3.8.3.3 | Stair for public use or with more than 50 occupants: minimum width | 1.2 m | Public use |
| K.3.8.3.3 | Interior stair in a dwelling: minimum width | 0.9 m | General |
| K.3.8.3.4 | Minimum tread depth | 280 mm | General |
| K.3.8.3.4 | Riser height | 100 to 180 mm | General |
| K.3.8.3.4 | 2c + h relationship (c = riser height, h = tread depth) | 620 to 640 mm | General |
| K.3.18.2.6 | Dwelling of up to 2 floors: minimum tread depth | 210 mm | General |
| K.3.18.2.6 | Dwelling of up to 2 floors: maximum riser height | 210 mm | General |
| K.3.8.3.5 | Landing: length equal to the stair width (maximum of 1.20 m required) | 1.2 m | General |
| K.3.8.3.5 | Maximum height difference between landings | 3.5 m | General |
| K.3.8.3.7 | Stair: minimum clear height | 2 m | General |
Ramps
| Numeral | Rule | Value | Applies to |
|---|---|---|---|
| K.3.8.6.2 | Evacuation ramp: maximum slope 1:12 (other pedestrian ramps 1:8) | 1:12 | General |
| K.3.8.6.3 | Ramp: maximum cross slope | 1:48 | General |
| K.3.8.6.4 | Ramp: minimum width | 1.1 m | General |
| K.3.8.6.5 | Ramp: minimum clear height | 2 m | General |
Egress and emergency lighting
| Numeral | Rule | Value | Applies to |
|---|---|---|---|
| K.3.5.1.3 | Dead-end corridor: maximum length | 6 m | General |
| K.3.9.2 | Emergency lighting: 10 lux average and 1 lux minimum | 10 lux | General |
Accessibility in buildings open to the public
These rules are not from Title K but from Decree 1538 of 2005, and they apply only to buildings open to the public.
| Article | Rule | Value | Applies to |
|---|---|---|---|
| Art. 9 | Building open to the public: at least one barrier-free entrance | 1 entrance | Public use |
| Art. 11 | Building open to the public: at least one accessible restroom | 1 restroom | Public use |
| Art. 11 | Accessible parking: 2% of the spaces, minimum 1 | 2% | Public use |
What changed after the copy consulted
The NSR-10 was adopted by Decree 926 of 2010 and has been amended several times. Among the amendments are Decrees 2113 of 2019, 1711 of 2021 and 1401 of 2023. We did not review which numerals of Title K they touched; that is why the rule is to check each figure against the current text before using it.
Worked example: does this stair comply?
Three hypothetical stairs against rules K.3.8.3.4 of the stairs table: minimum tread depth, riser height within the range, and 2c + h relationship within the range. The measurements are invented; the code does the calculation.
| Stair | 2c + h | Tread complies | Riser complies | 2c + h complies |
|---|---|---|---|---|
| Tread 280 mm, riser 170 mm | 620 mm | Yes | Yes | Yes |
| Tread 300 mm, riser 190 mm | 680 mm | Yes | No | No |
| Tread 250 mm, riser 160 mm | 570 mm | No | Yes | No |
Limits of this guide
- It is not a complete summary of Title K or of the NSR-10; topics and exceptions are missing.
- Some conditions depend on the use and on the number of occupants. Each row says what it applies to, but the classification of your building is yours.
- It does not replace the review of a licensed engineer or architect, or that of the curaduría (the urban-planning office) that issues the building license.
- What depends on the local land-use plan (plan de ordenamiento territorial: clear heights, minimum areas) is not here.
Frequently asked questions
Are these figures current?
They are those of the copy consulted. They were not checked against the Diario Oficial, and the regulation has had later amendments. Confirm them in the official text before using them in a design or an opinion.
Why are some rules you hear about on site missing?
Because only those the team could verify are published. Values from trade practice or from secondary sources were left out on purpose.
Does it apply to housing?
Each row says whether it is general or for public use. Interior stairs in dwellings have their own row; the classification of your building is yours to make.
What do I do if two sources give different figures?
Whatever the current official text says. If you are not sure, consult the curaduría or a licensed engineer.
Sources
- NSR-10, Title K (copy consulted by the Renka team, published by Findeter)
- Decree 1711 of 2021, partially amends the NSR-10 (Alcaldía de Bogotá, Régimen Legal) · read on 2026-10-23
- Decree 1401 of 2023, partially amends the NSR-10 (Ministerio de Vivienda) · read on 2026-10-23